Back to Top

1
Hi, Guest!

48363 Control Unit MicroLogic 5.0P, MasterPact NW Drawout, LSI

Update Terakhir
:
10 / 05 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail 48363 Control Unit MicroLogic 5.0P, MasterPact NW Drawout, LSI

Engine Control Unit

Control unit MicroLogic 5.0P, MasterPact NW drawout, LSI protections

Specifications

Main
Range : MasterPact
Range of product : MasterPact NW
Product or component type : Control unit
Trip unit name : MicroLogic 5.0 P
Trip unit technology : Electronic
Range compatibility :
- Masterpact NW08...40
- Masterpact NW40b...63
- Masterpact NW H10
- Masterpact NW H2 corrosion protection
Device application : Distribution
Number of poles :
- 3P
- 4P
Protected poles description :
- 4t
- 3t
- 3t + N/2
Trip unit protection functions : Selective protection
Protection type :
- For short time short-circuit protection
- for overload protection (long time)
- for instantaneous short-circuit protection
Trip unit rating :
- 800 A at 50 °C
- 1000 A at 50 °C
- 1250 A at 50 °C
- 1600 A at 50 °C
- 2000 A at 50 °C
- 2500 A at 50 °C
- 3200 A at 50 °C
- 4000 A at 50 °C
- 5000 A at 50 °C
- 6300 A at 50 °C
Network type : AC
Network frequency : 50/60 Hz
Circuit breaker mounting mode : Drawout

Complementary
Long-time pick-up adjustment type Ir (thermal protection) : Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range : 0.4...1 x In
Long-time protection delay adjustment type tr : Adjustable 9 settings
[tr] long-time protection delay adjustment range :
- 0.7…16.6 s at 7.2 x Ir
- 0.7…24 s at 6 x Ir
- 12.5…600 s at 1.5 x Ir
Thermal memory : 20 mn
Short-time protection pick-up adjustment type Isd : Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range : 1.5...10 x Ir
Short-time protection delay adjustment type tsd : Adjustable
[tsd] Short-time protection delay adjustment range :
- 0…0.4 s I²t=off
- 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii : Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range :
- Off
- 2...15 x In
Earth-leakage protection : Without
Zone selective interlocking ZSI : With
Local signalling :
- 3 LEDs (red) for electrical fault
- 1 LED (red) for internal error
Display type : Digital display
type of measurement : Power meter
Communication of data :
- Measurement readout
- Protection and alarm settings
- Maintenance indicators

Environment
Ambient air temperature for operation : -25…70 °C
Ambient air temperature for storage : -40…85 °C

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 6.9 cm
Package 1 Width : 7.9 cm
Package 1 Length : 21.5 cm
Package 1 Weight : 451.0 g

Contractual warranty
Warranty : 18 months
Tampilkan Lebih Banyak