Detail 59607 Base Unit S10UD For Sepam Series 20 - 24…250 V - With Advanced U
Base Unit
base unit S10UD for Sepam series 20 - 24…250 V - with advanced UMI
Specifications
Main
Range of product : Sepam series 20
Device short name : S10UD
User machine interface type : Advanced
Complementary
UMI indication :
- Metering and diagnosis data
- Status of logic imputs
- Alarms and operating messages
- Protection setting
- Sepam parameter setting
- Version of Sepam and remote modules
UMI control :
- Alarm acknowledgement
- Output testing
- Sepam reset
Display resolution : 128 x 64 pixels
Number of key : 9
Local signalling :
- 2 LEDs for Sepam operating status (front face)
- 9 LEDs for indication of parameters (front face)
Output type :
- Annunciation relay: 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 1 A cos φ > 0.3
- Annunciation relay: 127 V DC continuous current: 2 A breaking capacity: 0.5 A L/R < 20 ms
- Annunciation relay: 220 V DC continuous current: 2 A breaking capacity: 0.15 A L/R < 20 ms
- Annunciation relay: 24 V DC continuous current: 2 A breaking capacity: 2 A L/R < 20 ms
- Annunciation relay: 48 V DC continuous current: 2 A breaking capacity: 1 A L/R < 20 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 5 A cos φ > 0.3 making capacity: < 15 A for 200 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.5 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.7 A resistive making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.3 A resistive making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 4 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 6 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 4 A resistive making capacity: < 15 A for 200 ms
[Us] rated supply voltage :
- 110/240 V AC 47.5...63 Hz tolerance: - 20...10 % deactivated consumption: < 6 VA maximum consumption: < 15 VA
- 24/250 V DC tolerance: - 20...10 % deactivated consumption: < 4.5 W maximum consumption: < 8 W
Supply inrush current :
< 10 A for 10 ms at 24/250 V DC
< 15 A at 110/240 V AC
Mounting mode : Fixed
Mounting support : Plate
Height : 222 mm
Width : 176 mm
Depth : 129 mm
Net weight : 1.42 kg
Power frequency dielectric withstand : 2 kV during 1 min conforming to IEC 60255-5
[Uimp] rated impulse withstand voltage : 5 kV (1.2/50 µs) conforming to IEC 60255-5
Mechanical robustness :
- Earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
- Earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
- Jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
- Shocks de-energized (level: 2) : 30 Gn/11 ms conforming to IEC 60255-21-2
- Shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
- Vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
- Vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
- Vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
Environment
Standards
EN 50263 :
- CSA C22.2 No 0.17-00
- CSA C22.2 No 94-M91
- CSA C22.2 No 14-95
- UL 508
Product certifications :
- CE
- UL 508 file N° 212533
- C22.2 file N° 210625
Fire resistance : 650 °C conforming to IEC 60695-2-11
IP degree of protection :
- Other panels: IP20 conforming to IEC 60529
- Front panel: IP52 conforming to IEC 60529
NEMA degree of protection : Type 12 conforming to NEMA
Immunity to microbreaks : 10 ms
Electromagnetic compatibility :
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), III, 2.5 kV MC, 1 kV MD, conforming to IEC 60255-22-1
- Fast transient bursts: (immunity tests-conducted disturbances), A or B, 4kV, 2.5 kHz/2 kV, 5 kHz, conforming to IEC 60255-22-4
- Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz, conforming to IEC 61000-4-4
- Immunity to magnetic fields at network frequency: (immunity tests-radiated disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8
- Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80 MHz...2 GHz, conforming to IEC 61000-4-3
- Surges: (immunity tests-conducted disturbances), III, 2 kV MC, 1 kV MD, conforming to IEC 61000-4-5
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV MC and MD, conforming to ANSI C37.90.1
- 100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV MC, 1 kV MD, conforming to IEC 61000-4-12
- Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
- Conducted disturbance emission: (emission tests), B, conforming to EN 55022
- Disturbing field emission: (emission tests), conforming to IEC 60255-25
- Disturbing field emission: (emission tests), A, conforming to EN 55022
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV contact, conforming to ANSI C37.90.3
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to IEC 60255-22-2
- Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz, conforming to ANSI C37.90.1
- Immunity to conducted RF disturbances: (immunity tests-conducted disturbances), 10 V, conforming to IEC 60255-22-6
- Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...1 GHz, conforming to IEC 60255-22-3
- Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...1 GHz, conforming to ANSI C37.90.2 (1995)
- Voltage interruptions : (immunity tests-conducted disturbances), 100 %, 10 ms, conforming to IEC 60255-11
Climatic withstand :
- Continuous exposure to damp heat (in operation) : Ca: 10 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3
- Continuous exposure to damp heat (in storage) : Ca: 56 days, 93 % RH, 40 °C (104 °F) conforming to IEC 60068-2-3
- Exposure to cold (in operation) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
- Exposure to cold (in storage) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
- Exposure to dry heat (in operation) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
- Exposure to dry heat (in storage) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
- Influence of corrosion/gaz test 2 (in operation) : C: 21 days, 75 % RH, 25 °C (- 13 °F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
- Temperature variation with specified variation rate (in operation) : Nb: - 25 °C to 70 °C (- 13 °F to 158 °F) 5 °C/min (41 °F/min) conforming to IEC 60068-2-14
- Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.02 ppm NO2, 0.01 ppm Cl2 conforming to IEC 60068-2-60
- Salt mist (in operation) : Kb/2 conforming to IEC 60068-2-52
Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 12.200 cm
Package 1 Width : 27.200 cm
Package 1 Length : 26.700 cm
Package 1 Weight : 1.206 kg
Unit Type of Package 2 : S03
Number of Units in Package 2 : 3
Package 2 Height :30.000 cm
Package 2 Width : 30.000 cm
Package 2 Length : 40.000 cm
Package 2 Weight : 4.105 kg
Unit Type of Package 3 : P12
Number of Units in Package 3 : 24
Package 3 Height : 50.000 cm
Package 3 Width : 80.000 cm
Package 3 Length : 120.000 cm
Package 3 Weight : 44.840 kg