Detail 59835 Base Unit SEP060 For Sepam Series 60 - 24…250 V - With Basic UMI
Protection Relay
base unit SEP060 for Sepam series 60 - 24…250 V - with basic UMI
Specifications
Main
Range of product : Sepam series 60
Device short name : SEP060
User machine interface type : Without
Complementary
Output type :
- Annunciation relay: 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 1 A cos φ > 0.3
- Annunciation relay: 127 V DC continuous current: 2 A breaking capacity: 0.5 A L/R < 20 ms
- Annunciation relay: 220 V DC continuous current: 2 A breaking capacity: 0.15 A L/R < 20 ms
- Annunciation relay: 24 V DC continuous current: 2 A breaking capacity: 2 A L/R < 20 ms
- Annunciation relay: 48 V DC continuous current: 2 A breaking capacity: 1 A L/R < 20 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 5 A cos φ > 0.3 making capacity: < 15 A for 200 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.5 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.7 A resistive making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.3 A resistive making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 4 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 6 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 4 A resistive making capacity: < 15 A for 200 ms
[Us] rated supply voltage : 24/250 V DC tolerance: - 20...10 % maximum consumption: < 16 W
Supply inrush current : < 10 A for 10 ms at 24/250 V DC
Battery type : Lithium 3.6 V size: 1/2 AA
Battery life :
- 10 year(s) (Sepam energized)
- 8 year(s) (Sepam not energized)
Mounting mode : Fixed
Mounting support : Plate
Height : 222 mm
Width : 264 mm
Depth : 89.7 mm
Net weight : 2.4 kg
Power frequency dielectric withstand :
- 2 kV during 1 min conforming to IEC 60255-5
- 1 kV (indication output) during 1 min conforming to ANSI C37.90
- 1.5 kV (control output) during 1 min conforming to ANSI C37.90
[Uimp] rated impulse withstand voltage : 5 kV (1.2/50 µs) conforming to IEC 60255-5
Mechanical robustness :
- Earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
- Earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
- Jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
- Shocks de-energized (level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
- Shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
Vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
Vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6
Environment
Standards :
- CSA C22.2 No 14-95
- CSA C22.2 No 94-M91
- CSA C22.2 No 0.17-00
- UL 508
- EN 50263
Product certifications :
- C22.2 file N° 210625
- CE
- UL 508 file N° 212533
Fire resistance : 650 °C conforming to IEC 60695-2-11
IP degree of protection :
- Other panels: IP20 conforming to IEC 60529
- Front panel: IP52 conforming to IEC 60529
NEMA degree of protection : Type 12 conforming to NEMA
Immunity to microbreaks : 100 ms
Electromagnetic compatibility :
- Fast transient bursts: (immunity tests-conducted disturbances), A and B, 4kV, 2.5 kHz/2 kV, 5 kHz, conforming to IEC 60255-22-4
- Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz, conforming to IEC 61000-4-4
- Immunity to conducted RF disturbances: (immunity tests-conducted disturbances), III, 10 V, conforming to IEC 60255-22-6
- Immunity to magnetic fields at network frequency: (immunity tests-radiated disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8
- Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80 MHz...2 GHz, conforming to IEC 61000-4-3
- Surges: (immunity tests-conducted disturbances), III, 2 kV CM, 1 kV MD, conforming to IEC 61000-4-5
- Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
- Disturbing field emission: (emission tests), conforming to IEC 60255-25
- Disturbing field emission: (emission tests), A, conforming to EN 55022
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV contact, conforming to ANSI C37.90.3
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to IEC 60255-22-2
- Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz, conforming to ANSI C37.90.1
- Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...1 GHz, conforming to IEC 60255-22-3
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV MD, conforming to IEC 60255-22-1
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 2.5 kV MD, conforming to ANSI C37.90.1
- 100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV MD, conforming to IEC 61000-4-12
- Conducted disturbance emission: (emission tests), A, conforming to EN 55022
- Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...1 GHz, conforming to ANSI C37.90.2
- Voltage interruptions: (immunity tests-conducted disturbances), 100 % during 100 ms, conforming to IEC 60255-11
Climatic withstand :
- Continuous exposure to damp heat (in operation) : Cab: 10 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
- Continuous exposure to damp heat (in storage) : Cab: 56 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
- Continuous exposure to damp heat (in storage) : Db: 6 days, 95 % RH, 55 °C conforming to IEC 60068-2-30
- Exposure to cold (in operation) : Ad: - 25 °C conforming to IEC 60068-2-1
- Exposure to cold (in storage) : Ab: - 25 °C conforming to IEC 60068-2-1
- Exposure to dry heat (in operation) : Bd: 70 °C conforming to IEC 60068-2-2
- Exposure to dry heat (in storage) : Bb: 70 °C conforming to IEC 60068-2-2
- Salt mist (in operation) : Kb/2: 6 days conforming to IEC 60068-2-52
- Temperature variation with specified variation rate (in storage) : Nb: - 25 °C to 70 °C, 5 °C/min conforming to IEC 60068-2-14
- Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
- Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068-2-60
Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 28.5 cm
Package 1 Width : 19.0 cm
Package 1 Length : 36.0 cm
Package 1 Weight : 2.71 kg
Unit Type of Package 2 : S04
Number of Units in Package 2 : 3
Package 2 Height : 30.0 cm
Package 2 Width : 40.0 cm
Package 2 Length : 60.0 cm
Package 2 Weight : 10.792 kg