65294 Trip Unit MicroLogic 6.0P, ComPact NS630b To NS1600

Update Terakhir
:
11 / 05 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail 65294 Trip Unit MicroLogic 6.0P, ComPact NS630b To NS1600

Engine Control Unit

Trip unit MicroLogic 6.0P, ComPact NS630b to NS1600, drawout, selective and earth fault protections

Specifications

Main
Range : ComPact
Range of product : ComPact NS630b...1600
Product or component type : Trip unit
Trip unit name : MicroLogic 6.0 P
Trip unit technology : Electronic
Range compatibility : ComPact NS630b...1600
Device application : Distribution
Number of poles :
- 4P
- 3P
Protected poles description :
- 4t
- 3t
- 3t + N/2
Trip unit protection functions : Selective + earth-fault protection
Protection type :
- For overload protection (long time)
- for short time short-circuit protection
- for instantaneous short-circuit protection
- for earth fault
Trip unit rating :
- 630 A at 50 °C
- 800 A at 50 °C
- 1000 A at 50 °C
- 1250 A at 50 °C
- 1600 A at 50 °C
Network type : AC
Network frequency : 50/60 Hz
Circuit breaker mounting mode : Drawout

Complementary
Long-time pick-up adjustment type Ir (thermal protection) : Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range : 0.4...1 x In
Long-time protection delay adjustment type tr : Adjustable 9 settings
[tr] long-time protection delay adjustment range :
- 0.7…16.6 s at 7.2 x Ir
- 0.7…24 s at 6 x Ir
- 12.5…600 s at 1.5 x Ir
Thermal memory : 20 mn
Short-time protection pick-up adjustment type Isd : Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range : 1.5...10 x Ir
Short-time protection delay adjustment type tsd : Adjustable
[tsd] Short-time protection delay adjustment range :
- 0…0.4 s I²t=off
- 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii : Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range :
- 2...15 x In
- Off
Ground-fault protection pick-up adjustment type Ig : Adjustable 9 settings
[Ig] ground-fault protection pick-up adjustment range :
- 0.2...1 x In for 400 A < In < 1250 A
- 0.3...1 x In for In <= 400 A
- 500...1200 A for In >= 1250 A
Ground-fault protection time delay adjustment type tg : Adjustable
[tg] ground-fault protection time delay adjustment range :
- 0…0.4 s I²t=off
- 0.1…0.4 s I²t=on
Earth-leakage protection : Without
Zone selective interlocking ZSI : With
Local signalling :
- 3 LEDs (red) for electrical fault
- 1 LED (red) for internal error
Display type : Digital display
type of measurement : Power meter
Communication of data :
- Measurement readout
- Protection and alarm settings
- Maintenance indicators

Environment
Ambient air temperature for operation : -25…70 °C
Ambient air temperature for storage : -40…85 °C

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 6.8 cm
Package 1 Width : 8.0 cm
Package 1 Length : 21.5 cm
Package 1 Weight : 318.0 g

Contractual warranty
Warranty : 18 months