65578 ETA5S PROTECTION RELAY FOR MVS

Update Terakhir
:
05 / 07 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail 65578 ETA5S PROTECTION RELAY FOR MVS

Protection Relay

ETA5S PROTECTION RELAY FOR MVS

Specifications

Main
Range of product : EasyPact MVS
Product or component type : Control unit
Circuit breaker application :
- Standard
- Industrial
Poles description :
- 3P
- 4P
Protected poles description :
- 4D
- 3D
- 3D + N/2
Neutral position : Left
Network type : AC
Trip unit name : ETA5S
Trip unit technology : Micro-processor based
Trip unit rating : 800…4000 A

Complementary
Network frequency : 50/60 Hz
Mounting mode :
- Fixed
- Drawout
[Ue] rated operational voltage : 690 V AC 50/60 Hz conforming to IEC 60947-2
Neutral protection setting :
- Without protection (3D)
- 0.5 x Ir (3D + N/2)
- 1 x Ir (4D)
Trip unit protection functions : LSI
Protection type :
- Instantaneous short-circuit protection
- Short time short-circuit protection
- Overload protection (long time)
Fault indication :
- Overload
- Internal fault
- Short-circuit
- Earth fault
Long time pick-up adjustment type Ir : Adjustable 9 settings
Long time pick-up adjustment range : 0.4...1 x In
Long time delay adjustment type : Adjustable 9 settings
[tr] long-time delay adjustment range : 0.5…24 s (6 x Ir), accuracy: 0...- 20 %
Thermal memory : 20 minutes before and after tripping
Short-time pick-up adjustment type Isd : Adjustable 9 settings
[Isd] short-time pick-up adjustment range : 1.5...10 x Ir
Short-time delay adjustment type : Adjustable 5 settings
[tsd] short-time delay adjustment range : 100…400 ms
Instantaneous pick-up adjustment type Ii : Adjustable 9 settings
Instantaneous pick-up adjustment range :
- 2...15 x In, accuracy: +/- 10 %
- Off
Zone selective interlocking ZSI : With
Display type : Digital display
Type of measurement : Instantaneous current (I1, I2, I3, In), range: 0.2...1.2 In, accuracy: +/- 1.5 %
Maximum current (I1, I2, I3, In), range: 0.2...1.2 In, accuracy: +/- 1.5 %
Height : 200 mm
Width : 55 mm
Depth : 75 mm
Product weight : 0.213 kg

Environment
Ambient air temperature for operation : -5…70 °C
Ambient air temperature for storage : -25…85 °C

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 7.0 cm
Package 1 Width : 8.0 cm
Package 1 Length : 21.5 cm
Package 1 Weight : 252.0 g
Unit Type of Package 2 : S03
Number of Units in Package 2 : 15
Package 2 Height : 30.0 cm
Package 2 Width : 30.0 cm
Package 2 Length : 40.0 cm
Package 2 Weight : 4.2 kg
Unit Type of Package 3 : P12
Number of Units in Package 3 : 240
Package 3 Height : 75.0 cm
Package 3 Width : 80.0 cm
Package 3 Length : 120.0 cm
Package 3 Weight : 79.2 kg