DIXELL DIGITAL CONTROLLER XC1011-1C10F EMERSON

DIGITAL CONTROLLER FOR SIMULTANEOUS MANAGEMENT OF UP TO 8 COMPRESSORS AND FANS

Specifications

Generals: Display: LCD on VGC810

Power supply: 24Vac/dc

Probe inputs: Suction: 4÷20mA, 0÷5V, NTC, PTC - Suction 2: 4÷20mA, 0÷5V, NTC, PTC - Condensing: 4÷20mA, 0÷5V, NTC, PTC - Condensing 2: 4÷20mA, 0÷5V, NTC, PTC - Auxiliary: NTC, PTC - Auxiliary 2: NTC, PTC - Auxiliary 3: NTC, PTC - Auxiliary 4: NTC, PTC

Relay outputs: Loads: 11 x 7A configurable - Alarms: 2 x 8A

Other outputs: Inverter-compressor: 2 x 4÷20mA/0÷10V optional - Inverter-fans: 2 x 4÷20mA/0÷10V optional - Hot Key / Prog Tool Kit output: present - Serial output: RS485

Other: Alarms: last 100 - Remote display output: VGC810 - Buzzer: on keyboard

Data storing: on the non-volatile memory (EEPROM)

Operating temperature: 0÷60 °C

Storage temperature: -30÷85°C

Relative humidity: 20÷85% (no condensing)

Resolution: 1/10°C1/100bar

Accuracy: better than 1% of F.S.

Digital inputs: 19 x configurable

 

Features

  • Scroll, semi-hermetic, multi stages, with different power and screw compressor management
  • Subcritical CO2 regulation
  • Compressor unloading in case of high condensing pressure alarm
  • Suction superheat calculation with alarm management and possible stop of compressors
  • Valve management based on superheating value
  • Alarm management with absolute and relative pressure
  • Electronic pressure-switch management
  • Dynamic set point for energy saving
  • Sub-cooling management
  • Hourly run time signals for maintenance
  • Hot Key for quick and easy programming
  • Serial connection to monitoring systems

 

Tampilkan Lebih Banyak