Detail DPDQ502000 - Carel Duct Mounting VOC
Sensor Controller
DPDQ502000 - Carel Duct mounting VOC and CO2 sensor with a 0 to 10 Vdc output
DPDQ502000 - Duct mounting VOC and CO2 sensor with a 0 to 10 Vdc output Carel Duct mounting VOC and CO2 Air quality sensor with a 0..10V output -TECHNICAL FEATURES - ACTIVE AIR QUALITY SENSORS DUCT VERSION
DPDQ306000 (VOC)
Sensor : VOC sensor (metal oxide)
Measuring range : 0…100% air quality; referred to calibrating gas
Output signal : 0-10 V (0 V=clean air, 10 V=polluted air) o 4…20 mA (selectable via jumper)
Measuring accurancy : ± 20% of final value (referred to calibrating gas)
Long-term stability : <10% / per year
Sensor protection : sinter filter, exchangeable, screwed, easy to clean
DPDQ402000 (CO2)
Sensor CO2 : optical sensor
Measuring CO2 : 0…2000 ppm CO2
Output CO2 : 0-10 v
Measuring accurancy CO2 : ± 30 ppm, ± 5% of final value
Long-term stability : + 1% of final value per year
DPDQ502000 (VOC+CO2)
Air quality sensor : VOC sensor (metal oxide)
Measuring range, air quality
0…100% (mixed gas pollution referred to calibrating gas)
Output air quality : 0-10 V (0 V=clean air, 10 V=polluted air)
Measuring accuracy, air quality : ± 20% of final value (referrred to calibrating gas)
Common features
Power supply : 24 Vac/15-36 Vdc
Ambient temperature : 0…+50 °C
Electrical connection : 0.14 – 1.5 mm2 via screw terminals on circuit board
Warm-up period : 1 hour
Installation : by mounting flange, plastic and galvanised steel optional
Protection type : IP65 (according to IEC 529)
Tampilkan Lebih Banyak