Detail F-SM6R-DM2-A1 SM6-24 DM2 Mot220Vac,VTground,CT0.5rat100-200,T20,PM5560
AIS Insulation
SM6-24 DM2 Mot220Vac,VTground,CT0.5rat100-200,T20,PM5560,2CTB cubicle-VTBcubicle
Specifications
Main
Range of product : SM6
Technology type : Air insulated switchgear
device short name : DM2
Product or component type : Cubicle
Internal arc classification :
- AFL downward exhaust gas
- AFL upward exhaust gas
Exhaust gas :
- Exhaust gas downward
- Exhaust gas upward
Internal arc protection : 12.5 kA 1 s
Rated frequency (fr) : 50 Hz
Rated voltage (Ur) : 24 kV
Rated lightning impulse withstand voltage (Up) : 125 kV peak
Rated short-duration power-frequency withstand voltage [Ud] :28 kV rms 50 Hz for 1 min
Rated continuous current (Ir) : 630 A
Rated short-time withstand current (Ik) : 16 kA rms 1 s
Standards :
-IEC 62271-200
-IEC 62271-100:2012
- GOST-R 52565:2006
Complementary
Secondary current transformer :
- 5 A 16 kA 30 VA at class 0.5
- 5 A 16 kA 7.5 VA at class 5P, 15
Primary voltage transformer : 15...20 kV/V3
Secondary voltage transformer : 110 V/V3 30…50 VA class 0.5
Bus rated current : 630 A
Type of operator :
- CS
- Spring return RI type push-button circuit breaker
Rated supply voltage of auxiliary and control circuits (Ua) : 220 V AC/DC motor
Additional device type :
- Power meter for PM5560
- Protection relay for Easergy P3
Protection type : Circuit breaker
CB name : SF1 type 1
CB installation : Disconnectable
CB operating position : Left-hand side (B1)
Mass : 400 kg
Width : 750 mm
Depth : 1220 mm
Environment
Ambient air temperature for operation : -5…40 °C
Ambient air temperature for storage : -40…70 °C
IP degree of protection : IP3x
Vibration resistance :
- 0.5 gn horizontal
- 0.4 gn vertical
Operating altitude : <= 1000 m
Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 123.0 cm
Package 1 Width : 75.0 cm
Package 1 Length : 160.0 cm
Package 1 Weight : 355.0 kg
Tampilkan Lebih Banyak