Back to Top

1
Hi, Guest!
  • SCHNEIDER ELECTRIC
  • GVL200K500DS Galaxy VL UPS 200 scalable to 500 kW, 400/480V, Start-up

GVL200K500DS Galaxy VL UPS 200 Scalable To 500 KW, 400/480V, Start-up

Update Terakhir
:
10 / 10 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail GVL200K500DS Galaxy VL UPS 200 Scalable To 500 KW, 400/480V, Start-up

UPS (Uninterruptible Power Supply)

Galaxy VL UPS 200 scalable to 500 kW, 400/480V, Start-up 5x8

Specifications

Overview
Presentation : Highly efficient, modular, high-density 200kW (400/480V) 3-phase UPS that is scalable up to 500kW. It delivers top performance for medium, large, and edge data centers, as well as critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service.
Lead time : Special Order - Call for Quoted Lead Times

Main
Main Input Voltage :
- 380 V 3 phases
- 400 V 3 phases
- 415 V 3 phases
- 440 V 3 phases
- 480 V 3 phases
Main Output Voltage :
- 380 V 3 phases
- 400 V 3 phases
- 415 V 3 phases
- 440 V 3 phases
- 480 V 3 phases
Other Output Voltage :
- 400 V
- 480 V
Rated power in W : 200 kW
Rated power in VA : 200 kVA
Battery type :
- Li-Ion (Lithium-Ion)
- VRLA
- Ni-Cd (Nickel-Cadmium)

Batteries & Runtime
Efficiency : View Efficiency Graphaction
Discharge battery voltage : 384 V

General
Number of power module : 4
Number of power module free slots : 6
Redundant : Yes

Physical
Colour : White
Height : 197 cm
Width : 85 cm
Depth : 92.5 cm
Net weight : 550 kg

Input
Network frequency : 40...70 Hz
Max short time withstand current : 65 kA
Input harmonic distortion : Less than 5 % for full load
Load power factor : 0.5 leading to 0.5 lagging without derating

Output
Maximum configurable power in W : 500 kW
Crest factor : 3
Output harmonic distortion : < 1% linear load and < 5% non-linear load
Output overload operation : 10 minutes at 125% and 60 seconds at 150%
Maximum configurable power in VA : 500 kVA

Conformance
Product certifications :
- IEC 62040-1-1
- UL 1778 5th edition
- IEC 62040-2
- IEC 62040-3
- VFI-SS-111
- FCC Class B
- ENERGY STAR V2.0 (USA)
Standards : IEC 60721-4-2 level 2M2

Environmental
Ambient air temperature for operation : 0…40 °C
Relative humidity : 0…95 % non-condensing
Operating altitude : 0...3000 m
Ambient air temperature for storage : -25…55 °C
Storage Relative Humidity : 10…80 % non-condensing
IP degree of protection : IP20

Communications & Management
control panel : Touch screen LCD user interface

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 2145 mm
Package 1 Width : 1100 mm
Package 1 Length : 950 mm
Package 1 Weight : 620 kg

Contractual warranty
Warranty : 1 year on-site repair or replace with factory authorized Start-Up
Tampilkan Lebih Banyak
Kontak Kami