Back to Top

1
Hi, Guest!
  • SCHNEIDER ELECTRIC
  • GVMPB200KHS Galaxy VM 200 kVA UPS Parallel 400-400 V with Backfeed pro

GVMPB200KHS Galaxy VM 200 KVA UPS Parallel 400-400 V With Backfeed Pro

Update Terakhir
:
10 / 10 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail GVMPB200KHS Galaxy VM 200 KVA UPS Parallel 400-400 V With Backfeed Pro

UPS (Uninterruptible Power Supply)

Galaxy VM 200 kVA UPS Parallel 400-400 V with Backfeed protection, Start up 5x8

Specifications

Overview
Presentation : Highly compact, energy efficient 3-phase UPS for data center, facility and industrial applications. To be used with external battery cabinets.
Lead time : Usually Ships within 2 Weeks

Main
Main Input Voltage : 400 V 3 phases
Other Input Voltage :
- 380 V
- 415 V
Main Output Voltage : 400 V 3 phases
Other Output Voltage :
- 380 V
- 415 V
Rated power in W : 180 kW
Rated power in VA : 200 kVA
Output connector type :
- Hard wire 4-wire (3P + E) 1
- Hard wire 5-wire (3P + N + E) 1
Battery type : External battery system
Provided equipment :
- Built-in modbus protocol adapter
- Dust filter
- Installation guide
- Integrated network management
- Seismic compliance
- Top and bottom cable entry

Batteries & Runtime
Efficiency : View Efficiency Graphaction
Battery voltage : 480 V
Discharge battery voltage : 384 V
Max current discharge : 393 A
Battery power in VAH : 0 VAh runtime
Extended runtime : 0

General
Bypass voltage tolerance : +/- 10 % settable from +/- 4/6/8 and 10 %
Max bypass input current : 289 A
Bypass current protection : 400 A
Redundant : No

Physical
Colour : White
Height : 197 cm
Width : 105.2 cm
Depth : 85.4 cm
Net weight : 724 kg
USB compatible : No

Input
Network frequency : 40...70 Hz
Input voltage limits :
- 250...600 V adjustable
- 320...456 V 380 V
- 320...480 V 400 V
- 320...498 V 415 V
Maximum input current : 328 A
Switching current capacity : 400 A
Max short time withstand current : 65 kA
Input harmonic distortion : Less than 3 % for full load
Input protection type : GL fuse
inrush current : 200 A peak
Load power factor : 0.5 leading to 0.5 lagging
Input Power Factor at Full Load : 1

Output
Maximum configurable power in W : 180 kW
Harmonic distortion : Less than 2 %
Output frequency :
- 50/60 Hz +/- 1 Hz sync to mains
- 50/60 Hz +/- 1 Hz unsynchronised
Crest factor : Unlimited
Wave type : Sine wave
Output voltage tolerance : +/- 1% static and +/- 3% at 100% load step
Output harmonic distortion : < 2% linear load and < 3% non-linear load
Output overload operation : 10 minutes at 125% and 60 seconds at 150%
Neutral output current : 289 A
bypass type : Built-in static bypass
Maximum configurable power in VA : 200 kVA

Conformance
Product certifications :
- C-Tick
- CE
- ETL
- RCM
Standards :
- EN/IEC 62040-1
-EN/IEC 62040-2
- EN/IEC 62040-3
- IBC 2012 and CBC2013 to Sds=2.02g
- ISTA 2B
- OSHPD
- UL 1778

Environmental
Ambient air temperature for operation : 0…40 °C
Relative humidity : 0…95 %
Operating altitude : 0...3333 ft
Ambient air temperature for storage : -25…55 °C
Storage Relative Humidity : 0…95 %
Storage altitude : 0.00…14999.82 m
Acoustic level : 65 dBA
Heat dissipation : 24570 Btu/h
IP degree of protection : IP20

Communications & Management
Free slots : 2
control panel : 7" touch screen display
Emergency power off : Yes

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 215.6 cm
Package 1 Width : 106 cm
Package 1 Length : 149 cm
Package 1 Weight : 770 kg

Contractual warranty
Warranty : 1 year on-site repair or replace with factory authorized Start-Up