UPS (Uninterruptible Power Supply)

Galaxy VS UPS 60kW 400V with N+1 power module for external batteries, Start-up 5x8

Specifications

Overview
Presentation : Highly efficient, easy-to-deploy 60kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Includes 5x8 start-up service and one additional power module for N+1 redundancy.
Lead time : Usually Ships within 2 Weeks
Main
Main Input Voltage : 400 V 3 phases
Other Input Voltage :
- 380 V
- 415 V
Main Output Voltage : 400 V 3 phases
Rated power in W : 60 kW
Rated power in VA : 60 kVA
Battery type :
- External battery system
- Li-Ion (Lithium-Ion)
- VRLA
Provided equipment :
- Dust filter
- EcoStruxure IT ready (UPS)
- Installation guide
- Integrated network management
- Power modules ship installed
- Start-up service

Batteries & Runtime
Max current discharge : 163 A

General
Bypass voltage tolerance : +/- 10 %
Redundant : Yes

Physical
Colour : White
Height : 148.5 cm
Width : 52.1 cm
Depth : 84.7 cm
Net weight : 290 kg

Input
Network frequency : 40...70 Hz
Input voltage limits : 340...460 V 400 V
Maximum input current : 08 A
Max short time withstand current : 65 kA
Input harmonic distortion : Less than 3 % for full load
Load power factor : From 0.7 leading to 0.7 lagging without any derating

Output
Maximum configurable power in W : 60 kW
Output frequency :
- 50 Hz sync to mains
- 60 Hz sync to mains
- 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
- 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
Crest factor : 2.5
Wave type : Sine wave
Output voltage tolerance : +/-1% after 50ms
Output harmonic distortion : < 1% linear load and < 5% non-linear load
Output overload operation : 10 minutes at 125% and 60 seconds at 150%
bypass type : Built-in static bypass
Maximum configurable power in VA : 60 kVA

Conformance
Standards :
- EN/IEC 62040-1
- EN/IEC 62040-2
- FCC part 15 class A
- IEC 60721-4-2 level 2M2
- UL 1778 5th edition

Environmental
Ambient air temperature for operation : 0…40 °C
Relative humidity : 0…95 % non-condensing
Operating altitude : 0...3300 ft
Ambient air temperature for storage : -25…55 °C
Storage Relative Humidity : 10…80 % non-condensing
Acoustic level : 68 dBA
Heat dissipation : 6150 Btu/h
IP degree of protection : IP21

Communications & Management
control panel : Touch screen LCD user interface

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 168 cm
Package 1 Width : 99 cm
Package 1 Length : 64 cm
Package 1 Weight : 315 kg

Contractual warranty
Warranty : 1 year on-site repair or replace with factory authorized Start-Up
Tampilkan Lebih Banyak