We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail LC1D32BD TeSys D Contactor - 3P(3 NO) - AC-3 -

Contactor

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 24 V DC coil

Deskripsi

Kontaktor TeSys Deca, 3 kutub (3NO), untuk aplikasi kontrol motor hingga 32A/690V AC-3/3e (15kW@400V). Menyediakan koil DC 24V dengan modul penekan transien, kontak bantu internal 1NO+1NC (bersertifikasi cermin NC), koneksi dengan terminal klem sekrup. Untuk kecepatan operasi hingga 3600 siklus/jam dan lingkungan hingga 60°C, memberikan keandalan dan daya tahan tinggi. Kompak (lebar 45mm), pemasangan rel DIN atau pemasangan sekrup. Bersertifikasi multi standar (IEC, UL, CSA, CCC, EAC, Marine), sesuai dengan Green Premium (RoHS/REACh).

Specifications

Main
Range of product : TeSys Deca
Product or component type : Contactor
Device short name : LC1D
contactor application :
- Resistive load
- Motor control
Utilisation category :
AC-3
AC-1
AC-4
AC-3e
poles description : 3P
[Ue] rated operational voltage :
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current :
32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage : 24 V DC

Complementary
Motor power kW :
7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
15 kW at 380...400 V AC 50/60 Hz (AC-3)
15 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
7.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
15 kW at 380...400 V AC 50/60 Hz (AC-3e)
15 kW at 415...440 V AC 50/60 Hz (AC-3e)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp :
2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
20 hp at 460/480 V AC 50/60 Hz for 3 phases motors
25 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code : LC1D
Pole contact composition : 3 NO
Protective cover : With
[Ith] conventional free air thermal current :
10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
Irms rated making capacity :
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity : 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current :
260 A 40 °C - 10 s for power circuit
430 A 40 °C - 1 s for power circuit
60 A 40 °C - 10 min for power circuit
138 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating :
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance : 2 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole :
2 W AC-3
5 W AC-1
2 W AC-3e
[Ui] rated insulation voltage :
- Power circuit: 690 V conforming to IEC 60947-4-1
- Power circuit: 600 V CSA certified
- Power circuit: 600 V UL certified
- Signalling circuit: 690 V conforming to IEC 60947-1
- Signalling circuit: 600 V CSA certified
- Signalling circuit: 600 V UL certified
Overvoltage category : III
Pollution degree : 3
[Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947
Safety reliability level :
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability : 30 Mcycles
Electrical durability :
1.65 Mcycles 32 A AC-3 at Ue <= 440 V
1.4 Mcycles 50 A AC-1 at Ue <= 440 V
1.65 Mcycles 32 A AC-3e at Ue <= 440 V
Control circuit type : DC standard
Coil technology : Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits :
0.1...0.25 Uc (-40…70 °C):drop-out DC
0.7...1.25 Uc (-40…60 °C):operational DC
1...1.25 Uc (60…70 °C):operational DC
Inrush power in W : 5.4 W (at 20 °C)
Hold-in power consumption in W : 5.4 W at 20 °C
Operating time :
63 ±15 % ms closing
20 ±20 % ms opening
Time constant : 28 ms
Maximum operating rate : 3600 cyc/h 60 °C
Maximum operating rate : 3600 cyc/h at 60 °C
Connections - terminals :
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
- Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable end
- Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end
- Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end
- Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable end
- Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable end
- Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
Tightening torque :
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition : 1 NO + 1 NC
Auxiliary contacts type :
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency : 25...400 Hz
Minimum switching voltage : 17 V for signalling circuit
Minimum switching current : 5 mA for signalling circuit
Insulation resistance : > 10 MOhm for signalling circuit
Non-overlap time :
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
mounting support :
- Rail
- Plate

Environment
Standards :
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 60947-4-1
- IEC 60335-1:Clause 30.2
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- CSA C22.2 No 60947-4-1
Product certifications :
- UL
- CCC
- CSA
- Marine
- UKCA
- EAC
- CB Scheme
IP degree of protection : IP20 front face conforming to IEC 60529
Protective treatment : TH conforming to IEC 60068-2-30
Climatic withstand :
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device :
-40…60 °C
60…70 °C with derating
Operating altitude : 0...3000 m
Fire resistance : 850 °C conforming to IEC 60695-2-1
Flame retardance : V1 conforming to UL 94
Mechanical robustness :
- Vibrations contactor open (2 Gn, 5...300 Hz)
- Vibrations contactor closed (4 Gn, 5...300 Hz)
- Shocks contactor closed (15 Gn for 11 ms)
- Shocks contactor open (8 Gn for 11 ms)
Height : 85 mm
Width : 45 mm
Depth : 101 mm
Net weight : 0.535 kg

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 5.000 cm
Package 1 Width : 9.200 cm
Package 1 Length : 11.200 cm
Package 1 Weight : 585.000 g
Unit Type of Package 2 : S02
Number of Units in Package 2 : 15
Package 2 Height : 15.000 cm
Package 2 Width : 30.000 cm
Package 2 Length : 40.000 cm
Package 2 Weight : 9.055 kg
Unit Type of Package 3 : P06
Number of Units in Package 3 : 240
Package 3 Height : 75.000 cm
Package 3 Width : 60.000 cm
Package 3 Length : 80.000 cm
Package 3 Weight : 154.500 kg