Back to Top

1
Hi, Guest!
  • SCHNEIDER ELECTRIC
  • LC1D38M7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 220 V A

LC1D38M7 TeSys D Contactor - 3P(3 NO) - AC-3 -

Update Terakhir
:
05 / 09 / 2024
Min. Pembelian
:
1 Batang

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail LC1D38M7 TeSys D Contactor - 3P(3 NO) - AC-3 -

Contactor

LC1D38M7 , TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 220 V AC 50/60 Hz coil

Deskripsi
Kontaktor TeSys Deca, 3 kutub (3NO), untuk aplikasi kontrol motor hingga 38A/690V AC-3/3e (18,5 kW@400V). Menyediakan koil AC 220V 50/60Hz, kontak bantu internal 1NO+1NC (bersertifikasi cermin NC), koneksi dengan terminal klem sekrup. Untuk kecepatan operasi hingga 3600 siklus/jam dan lingkungan hingga 60°C, kontaktor ini memberikan keandalan dan daya tahan yang tinggi. Ringkas (lebar 45mm), pemasangan rel DIN atau pemasangan sekrup. Bersertifikasi multi standar (IEC, UL, CSA, CCC, EAC, Marine), sesuai dengan Green Premium (RoHS/REACh).

Spesifikasi

Main
Range :
- TeSys
- TeSys Deca
Range of product : TeSys Deca
Product or component type : Contactor
Device short name : LC1D
contactor application :
- Motor control
- Resistive load
Utilisation category :
- AC-4
- AC-1
- AC-3
- AC-3e
poles description : 3P
[Ue] rated operational voltage :
- Power circuit: <= 690 V AC 25...400 Hz
- Power circuit: <= 300 V DC
[Ie] rated operational current :
50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage : 220 V AC 50/60 Hz

Complementary
Motor power kW :
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 380...400 V AC 50/60 Hz (AC-3)
9 kW at 220...230 V AC 50/60 Hz (AC-3)
18.5 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
18.5 kW at 380...400 V AC 50/60 Hz (AC-3e)
9 kW at 220...230 V AC 50/60 Hz (AC-3e)
18.5 kW at 415...440 V AC 50/60 Hz (AC-3e)
Motor power hp :
10 hp at 230/240 V AC 50/60 Hz for 3 phases motors
10 hp at 200/208 V AC 50/60 Hz for 3 phases motors
5 hp at 240 V AC 50/60 Hz for 1 phase motors
20 hp at 480 V AC 50/60 Hz for 3 phases motors
25 hp at 600 V AC 50/60 Hz for 3 phases motors
Compatibility code : LC1D
Pole contact composition : 3 NO
Protective cover : With
[Ith] conventional free air thermal current :
10 A (at 60 °C) for signalling circuit
50 A (at 60 °C) for power circuit
Irms rated making capacity :
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity : 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current :
60 A 40 °C - 10 min for power circuit
430 A 40 °C - 1 s for power circuit
150 A 40 °C - 1 min for power circuit
310 A 40 °C - 10 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating :
10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance : 2 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole :
5 W AC-1
3 W AC-3
3 W AC-3e
[Ui] rated insulation voltage :
- Power circuit: 600 V CSA certified
- Power circuit: 600 V UL certified
- Signalling circuit: 690 V conforming to IEC 60947-1
- Signalling circuit: 600 V CSA certified
- Signalling circuit: 600 V UL certified
- Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category : III
Pollution degree : 3
[Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947
Safety reliability level :
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability : 15 Mcycles
Electrical durability :
1.4 Mcycles 50 A AC-1 at Ue <= 440 V
1.4 Mcycles 38 A AC-3 at Ue <= 440 V
1.4 Mcycles 38 A AC-3e at Ue <= 440 V
Control circuit type : AC at 50/60 Hz
Coil technology : Without built-in suppressor module
Control circuit voltage limits :
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA :
70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA :
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation : 2…3 W at 50/60 Hz
Operating time :
4...19 ms opening
12...22 ms closing
Maximum operating rate : 3600 cyc/h 60 °C
Maximum operating rate : 3600 cyc/h at 60 °C
Connections - terminals :
- Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
- Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable end
- Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end
- Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end
- Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable end
- Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable end
- Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
Tightening torque :
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
- Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
- Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition : 1 NO + 1 NC
Auxiliary contacts type :
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency : 25...400 Hz
Minimum switching voltage : 17 V for signalling circuit
Minimum switching current : 5 mA for signalling circuit
Insulation resistance : > 10 MOhm for signalling circuit
Non-overlap time :
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
mounting support :
- Rail
- Plate

Environment
Standards :
- CSA C22.2 No 14
- EN 60947-4-1
- EN 60947-5-1
- IEC 60947-4-1
- IEC 60947-5-1
- UL 60947-4-1
- IEC 60335-1:Clause 30.2
- IEC 60335-2-40:Annex JJ
- UL 60335-2-40:Annex JJ
- CSA C22.2 No 60947-4-1
Product certifications :
- UL
- CCC
- CSA
- Marine
- UKCA
- EAC
- CB Scheme
IP degree of protection : IP20 front face conforming to IEC 60529
Protective treatment : TH conforming to IEC 60068-2-30
Climatic withstand :
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device :
-40…60 °C
60…70 °C with derating
Operating altitude : 0...3000 m
Fire resistance : 850 °C conforming to IEC 60695-2-1
Flame retardance : V1 conforming to UL 94
Mechanical robustness :
- Vibrations contactor open (2 Gn, 5...300 Hz)
- Vibrations contactor closed (4 Gn, 5...300 Hz)
- Shocks contactor closed (15 Gn for 11 ms)
- Shocks contactor open (8 Gn for 11 ms)
Height : 85 mm
Width : 45 mm
Depth : 92 mm
Net weight : 0.38 kg

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 5 cm
Package 1 Width : 9.3 cm
Package 1 Length : 11.5 cm
Package 1 Weight : 413 g
Unit Type of Package 2 : S02
Number of Units in Package 2 : 20
Package 2 Height : 15 cm
Package 2 Width : 30 cm
Package 2 Length : 40 cm
Package 2 Weight : 8.576 kg
Unit Type of Package 3 : P06
Number of Units in Package 3 : 160
Package 3 Height : 45 cm
Package 3 Width : 60 cm
Package 3 Length : 80 cm
Package 3 Weight : 76.608 kg