Back to Top

1
Hi, Guest!
  • SCHNEIDER ELECTRIC
  • LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V

LC1D65AM7 TeSys D Contactor - 3P(3 NO) - AC-3 -

Update Terakhir
:
04 / 09 / 2024
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail LC1D65AM7 TeSys D Contactor - 3P(3 NO) - AC-3 -

Contactor

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC 50/60 Hz coil

Deskripsi
Kontaktor TeSys Deca, 3 kutub (3NO), untuk aplikasi kontrol motor hingga 65A/440V AC-3/3e (30kW@400V). Menyediakan koil AC 220V 50/60Hz, kontak bantu internal 1NO+1NC (bersertifikasi cermin NC), sambungan daya melalui konektor sekrup EverLink BTR, sambungan kontrol melalui terminal klem sekrup. Untuk kecepatan operasi hingga 3600 siklus/jam dan lingkungan hingga 60°C, memberikan keandalan dan daya tahan tinggi. Kompak (lebar 55mm), pemasangan rel DIN atau pemasangan sekrup. Bersertifikasi multi standar (IEC, UL, CSA, CCC, EAC, Marine), sesuai dengan Green Premium (RoHS/REACh).

Specifications

Main
Range :
- TeSys
- TeSys Deca
Range of product : TeSys Deca
Product or component type : Contactor
Device short name : LC1D
contactor application :
- Motor control
- Resistive load
Utilisation category :
AC-4
AC-1
AC-3
AC-3e
poles description : 3P
[Ue] rated operational voltage :
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current :
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage : 220 V AC 50/60 Hz

Complementary
Motor power kW :
11 kW at 400 V AC 50/60 Hz (AC-4)
18.5 kW at 220...230 V AC 50/60 Hz (AC-3)
30 kW at 380...400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660...690 V AC 50/60 Hz (AC-3)
18.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
30 kW at 380...400 V AC 50/60 Hz (AC-3e)
37 kW at 500 V AC 50/60 Hz (AC-3e)
37 kW at 660...690 V AC 50/60 Hz (AC-3e)
Motor power hp :
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility code : LC1D
Pole contact composition : 3 NO
Protective cover : With
[Ith] conventional free air thermal current :
10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity :
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity :
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
640 A 40 °C - 10 s for power circuit
900 A 40 °C - 1 s for power circuit
110 A 40 °C - 10 min for power circuit
260 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating :
10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance : 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole :
9.6 W AC-1
6.3 W AC-3
6.3 W AC-3e
[Ui] rated insulation voltage :
- Power circuit: 600 V CSA certified
- Power circuit: 600 V UL certified
- Signalling circuit: 690 V conforming to IEC 60947-1
- Signalling circuit: 600 V CSA certified
- Signalling circuit: 600 V UL certified
- Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category : III
Pollution degree : 3
[Uimp] rated impulse withstand voltage : 6 kV conforming to IEC 60947
Safety reliability level :
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability : 6 Mcycles
Electrical durability :
1.4 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V
Control circuit type : AC at 50/60 Hz standard
Coil technology : Without built-in suppressor module
Control circuit voltage limits :
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA :
140 VA 60 Hz cos phi 0.75 (at 20 °C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA :
13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation : 4…5 W at 50/60 Hz
Operating time :
4...19 ms opening
12...26 ms closing
Maximum operating rate : 3600 cyc/h 60 °C
Maximum operating rate : 3600 cyc/h at 60 °C
Connections - terminals :
- Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
- Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
- Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
- Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable end
- Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable end
- Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable end
- Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable end
- Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid without cable end
- Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid without cable end
Tightening torque
- Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver flat Ø 6 mm
- Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver Philips No 2
- Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm
- Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm
- Control circuit: 1.7 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
- Power circuit: 2.5 N.m - on EverLink BTR screw connectors - with screwdriver pozidriv No 2
Auxiliary contact composition : 1 NO + 1 NC
Auxiliary contacts type :
- type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
- type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency : 25...400 Hz
Minimum switching voltage : 17 V for signalling circuit
Minimum switching current : 5 mA for signalling circuit
Insulation resistance : > 10 MOhm for signalling circuit
Non-overlap time :
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
mounting support :
- Rail
- Plate

Environment
Standards :
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
CSA C22.2 No 14
UL 60947-4-1
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
IEC 60335-1:Clause 30.2
Product certifications :
- CCC
- UL
- CB Scheme
- CSA
- CE
- UKCA
- Marine
- EAC
IP degree of protection : IP20 front face conforming to IEC 60529
Protective treatment : TH conforming to IEC 60068-2-30
Climatic withstand :
- conforming to IACS E10 exposure to damp heat
- conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device :
-40…60 °C
60…70 °C with derating
Operating altitude : 0...3000 m
Fire resistance : 850 °C conforming to IEC 60695-2-1
Flame retardance : V1 conforming to UL 94
Mechanical robustness :
- Vibrations contactor open (2 Gn, 5...300 Hz)
- Vibrations contactor closed (4 Gn, 5...300 Hz)
- Shocks contactor closed (15 Gn for 11 ms)
- Shocks contactor open (10 Gn for 11 ms)
Height : 122 mm
Width : 55 mm
Depth : 120 mm
Net weight : 0.86 kg

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 6.300 cm
Package 1 Width : 13.500 cm
Package 1 Length : 15.300 cm
Package 1 Weight : 929.000 g
Unit Type of Package 2 : S02
Number of Units in Package 2 : 10
Package 2 Height : 15.000 cm
Package 2 Width : 30.000 cm
Package 2 Length : 40.000 cm
Package 2 Weight : 9.849 kg
Unit Type of Package 3 : P06
Number of Units in Package 3 : 160
Package 3 Height : 75.000 cm
Package 3 Width : 60.000 cm
Package 3 Length : 80.000 cm
Package 3 Weight : 165.408 kg
Tampilkan Lebih Banyak