Detail LC1K1610Q7 TeSys K Contactor - 3P - AC-3
Contactor ABB AX185-30
TeSys K contactor - 3P - AC-3 <= 440 V 16 A - 1 NO aux. - 380...400 V AC coil
Spesifikasi
Main
Range : TeSys
Product or component type : Contactor
Product name : TeSys K
device short name : LC1K
Device application : Control
Contactor application : Motor control
Complementary
Utilisation category :
- AC-3
- AC-1
- AC-3e
Poles description : 3P
power pole contact composition : 3 NO
[Ue] rated operational voltage :
- Power circuit: 690 V AC 50/60 Hz
- Signalling circuit: 690 V AC 50/60 Hz
[Ie] rated operational current :
- 16 A at <= 440 V AC-3 for power circuit
- 20 A at <= 690 V AC-1 for power circuit
- 16 A at <= 440 V AC-3e for power circuit
Control circuit type : AC at 50/60 Hz
[Uc] control circuit voltage : 380...400 V AC 50/60 Hz
Motor power kW :
- 4 kW at 480 V AC 50/60 Hz
- 4 kW at 500...600 V AC 50/60 Hz
- 4 kW at 660...690 V AC 50/60 Hz
- 5.5 kW at 440 V AC 50/60 Hz
- 4 kW at 220...230 V AC 50/60 Hz
- 7.5 kW at 380...415 V AC 50/60 Hz
Auxiliary contact composition : 1 NO
[Uimp] rated impulse withstand voltage : 8 kV
Overvoltage category : III
[Ith] conventional free air thermal current :
- 20 A (at 50 °C) for power circuit
- 10 A (at 50 °C) for signalling circuit
Irms rated making capacity :
- 110 A AC for signalling circuit conforming to IEC 60947
- 160 A AC for power circuit conforming to NF C 63-110
- 160 A AC for power circuit conforming to IEC 60947
Rated breaking capacity :
- 110 A at 440 V conforming to IEC 60947
- 80 A at 500 V conforming to IEC 60947
- 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current :
- 115 A 50 °C - 1 s for power circuit
- 105 A 50 °C - 5 s for power circuit
- 100 A 50 °C - 10 s for power circuit
- 75 A 50 °C - 30 s for power circuit
- 55 A 50 °C - 1 min for power circuit
- 50 A 50 °C - 3 min for power circuit
- 25 A 50 °C - >= 15 min for power circuit
- 80 A - 1 s for signalling circuit
- 90 A - 500 ms for signalling circuit
- 110 A - 100 ms for signalling circuit
Associated fuse rating :
- 25 A gG at <= 440 V for power circuit
- 25 A aM for power circuit
- 10 A gG for signalling circuit conforming to IEC 60947
- 10 A gG for signalling circuit conforming to VDE 0660
Average impedance : 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage :
- Power circuit: 600 V conforming to UL 508
- Power circuit: 690 V conforming to IEC 60947-4-1
- Signalling circuit: 690 V conforming to IEC 60947-4-1
- Signalling circuit: 690 V conforming to IEC 60947-5-1
- Signalling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signalling circuit: 600 V conforming to CSA C22.2 No 14
Insulation resistance : > 10 MOhm for signalling circuit
Inrush power in VA : 30 VA (at 20 °C)
Hold-in power consumption in VA : 4.5 VA (at 20 °C)
Heat dissipation : 1.3 W
Control circuit voltage limits :
- Operational: 0.85...1.1 Uc (at <50 °C)
- Drop-out: 0.2...0.75 Uc (at <50 °C)
Connections - terminals :
- Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
- Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
- Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
- Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
- Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
- Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Maximum operating rate : 3600 cyc/h
Auxiliary contacts type : Type instantaneous 1 NO
Signalling circuit frequency : <= 400 Hz
Minimum switching current : 5 mA for signalling circuit
Minimum switching voltage : 17 V for signalling circuit
Mounting support :
- Plate
- Rail
Tightening torque :
- 0.8…1.3 N.m - on screw clamp terminals Philips No 2
- 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm
- 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2
Operating time :
- 10...20 ms coil de-energisation and NO opening
- 10...20 ms coil energisation and NO closing
Safety reliability level :
- B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Non overlap distance : 0.5 mm
Mechanical durability : 10 Mcycles
Electrical durability :
- 1.3 Mcycles 16 A AC-3 at Ue <= 440 V
- 1.3 Mcycles 16 A AC-3e at Ue <= 440 V
Mechanical robustness :
- Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
- Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
- Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
- Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Height : 58 mm
Width : 45 mm
Depth : 57 mm
Product weight : 0.18 kg
Environment
Standards :
- EN/IEC 60947-4-1
- GB/T 14048.4
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
- JIS C8201-4-1
Product certifications :
- CB Scheme
- CCC
- UL
- CSA
- EAC
- CE
- UKCA
IP degree of protection : IP2X conforming to VDE 0106
Protective treatment :
- TC conforming to IEC 60068
- TC conforming to DIN 50016
Ambient air temperature for operation : -25…50 °C
Ambient air temperature for storage : -50…80 °C
Operating altitude : 2000 m without derating
Flame retardance : V1 conforming to UL 94
Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 6.600 cm
Package 1 Width : 4.800 cm
Package 1 Length
6.200 cm
Package 1 Weight : 177.000 g
Unit Type of Package 2 : S02
Number of Units in Package 2 : 50
Package 2 Height : 15.000 cm
Package 2 Width : 30.000 cm
Package 2 Length : 40.000 cm
Package 2 Weight : 9.252 kg
Contractual warranty
Warranty : 12 months
Tampilkan Lebih Banyak