Detail LV454444 External Power Supply Module, Input Voltage 200 V AC To 240 V
Power Supply Unit
external power supply module, input voltage 200 V AC to 240 V AC 50/60 Hz, output voltage 24 V DC, output current 1 A
Specifications
Main
Product or component type : External power supply module
Device application : Power supply
Range compatibility :
- Masterpact (MasterPact MTZ)
- Masterpact (MasterPact NT)
- Masterpact (MasterPact NW)
- ComPact (ComPact NSX)
- ComPact (ComPact NSX DC)
- ComPact (ComPact NS630b...1600)
- ComPact (ComPact NS1600b...3200)
- PowerPact (PowerPact H)
- PowerPact (PowerPact J)
- Po-werPact (PowerPact L)
- PowerPact (PowerPact P)
- PowerPact (PowerPact R)
Accessory / separate part type :
- Control units accessories
- Trip unit accessories
Complementary
Trip unit name : MicroLogic
Power supply type : Regulated switch mode
[Us] rated supply voltage : 200...240 V AC 50/60 Hz tolerance: +10 % -15 %
Input voltage limits : 170...264 V AC at 47.5…63 Hz
Output voltage : 24 V DC +/-5 %
Overvoltage category :
- IV confo'rming to IEC 62477-1
- III conforming to UL 61010-1
Power supply output current : 1 A
rated power in W : 24 W
Output protection type :
- Against overload, protection technology: manual reset
- Against overvoltage, protection technology: 30...32 V, manual reset
- Against short-circuits, protection technology: manual reset
- Thermal, protection technology: automatic reset
Inrush current : 20 A 2 ms
Efficiency : 85 %
Power dissipation in W : 4.2 W
Holding time : >= 20 ms 200...240 V AC
Permissible temporary current boost : 1.5 A (200 ms)
Connections - terminals :
- Screw type terminals, connection capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16
- Screw type terminals, connection capacity: 1 x 0.2...1 x 4 mm² AWG 24...AWG 12
Mounting support : 35 x 7.5 mm symmetrical DIN rail
operating position : Horizontal
Operating altitude : 0...2000 m
Name of test :
- Electrostatic discharges conforming to EN/IEC 61000-4-2
- Induced electromagnetic field conforming to EN/IEC 61000-4-6
- Magnetic field conforming to EN 61000-4-8
- Primary outage conforming to IEC 61000-4-11
- Radiated electromagnetic field conforming to EN/IEC 61000-4-3
- Rapid transient conforming to IEC 61000-4-4
- Surge conforming to EN/IEC 61000-4-5
- Radiated emissions conforming to EN 61000-6-3
- Conducted emissions on the power line conforming to EN 61000-6-3
Status LED : 1 LED (green) output voltage
Height : 90 mm
Width : 108 mm
Depth : 67.5 mm
Environment
Standards :
- UL 61010-1
- IEC 62477-1
Marking :
- EAC
- CE
- UL
Environmental characteristic :
- EMC conforming to EN/IEC 61000-6-2
- EMC conforming to EN/IEC 61000-6-3
- Safety conforming to IEC 62477-1
- Safety conforming to SELV
IP degree of protection :
- IP4X (front face) conforming to EN/IEC 60529
- IP2X (connection terminals) conforming to EN/IEC 60529-
- IP3x (housing) conforming to EN/IEC 60529
Ambient air temperature for operation : -25…70 °C
Ambient air temperature for storage : -50…85 °C
Relative humidity :
- 0…95 % during operation
- 0…95 % in storage
Dielectric strength :
- 3000 V between input and ground
- 3000 V between input and output
- 1500 V between output and ground
Compatibility code : CB_EXTERNAL_POWERSUPPLY
Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 7.5 cm
Package 1 Width : 11.1 cm
Package 1 Length : 12.7 cm
Package 1 Weight : 370.0 g
Unit Type of Package 2 : S03
Number of Units in Package 2 : 23
Package 2 Height : 30.0 cm
Package 2 Width :30.0 cm
Package 2 Length : 40.0 cm
Package 2 Weight : 8.95 kg
Unit Type of Package 3 : P12
Number of Units in Package 3 : 552
Package 3 Height : 105.0 cm
Package 3 Width : 80.0 cm
Package 3 Length :120.0 cm
Package 3 Weight : 226.8 kg
Contractual warranty
Warranty : 18 months
Tampilkan Lebih Banyak