Portable Ventilator

ClimaSys forced vent. IP54, 850m3/h, 115V, with outlet grille and filter G2

Keterangan

Ventilator motor Aksial ClimaSys CV. 115V 50Hz atau 60Hz. 145W 50Hz, 182W 60Hz. Laju aliran bebas dengan filter standar 944 m3/jam pada 50 Hz dan 983 m3/jam pada 60 Hz. 336x316x162mm. Dimensi potongan 291 x 291 mm. Kisi-kisi outlet termoplastik injeksi (ASA PC), Abu-abu RAL 7035. Terminal sambungan dengan kabel. 2 kisi pelindung pada permukaan depan dan belakang. Perlindungan IP54.

Specifications

Overview
Lead time : Usually Ships within 4 Weeks

Main
Range : ClimaSys
Product name : ClimaSys CV
Product or component type : Fan
Type of filter : Standard
Flow rate :
Free flow rate with standard filter: 983 m3/h at 50 Hz
Free flow rate with standard filter: 944 m3/h at 60 Hz
[Us] rated supply voltage : 103...122 V
Input voltage : 115 V 50/60 Hz

Complementary
Absorbed power :
- 145 W 50 Hz
- 182 W 60 Hz
[In] rated current :
- 1.279 A 50 Hz
- 1.6 A 60 Hz
Noise level < at : 77…78 dB
Bearing type : Ball
Height : 336 mm external:
Width : 316 mm external:
Depth : 162 mm external:
Cut-out dimensions : 291 x 291 mm
Net weight : 4.1 kg
Material : Outlet grille: injected thermoplastic (ASA PC)
Colour : Outlet grille: grey (RAL 7035)
Ambient air temperature for operation : -15…60 °C
Ambient air temperature for storage : -40…70 °C
Maximum pressure : 170 Pa flow rate 0 m³/h
Connections - terminals : Terminal block
IP degree of protection : IP54
Device composition :
- 1 axial motor
- 2 protective grille: on the front and rear surfaces
- 1 filter: front of axial motor
- 1 outlet grille: front
- 1 cut-out template
Condition of use :
- Filter must be cleaned and replaced regularly
- Overfrequent filter replacement should be avoided
- Outside temperature must be 5 °C lower than inside temperature
- Flow rates depends on the work point, see ProClima software
- Surrounding environment must be relatively clean

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 20.5 cm
Package 1 Width : 33 cm
Package 1 Length : 43 cm
Package 1 Weight : 4.608 kg
Unit Type of Package 2 : PAM
Number of Units in Package 2 : 50
Package 2 Height : 150 cm
Package 2 Width : 100 cm
Package 2 Length : 120 cm
Package 2 Weight : 243 kg

Contractual warranty
Warranty : 18 months