Back to Top

1
Hi, Guest!
  • CAREL
  • UA100HD301 - Carel Pump for Humifog Humidifier

UA100HD301 - Carel Pump For Humifog Humidifier

Update Terakhir
:
08 / 02 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail UA100HD301 - Carel Pump For Humifog Humidifier

Penjernih Udara, Dehumidifier, & Humidifier

UA100HD301 - Carel Pump for Humifog Humidifier, Adiabatic Humidifier, 100kg/hr single zone stainless pump.

Pompa stainless zona tunggal Humifog UA100HD301 - 100kg/jam adalah fungsi pemanasan/pendinginan ganda: unit zona tunggal humiFog dapat mendinginkan udara selama musim panas dan melembabkan selama musim dingin. Teknologi pendinginan evaporatif tidak langsung memastikan penghematan energi yang signifikan, artinya investasi dapat dibayar kembali dengan sangat cepat. Humifog singlezone cocok untuk semua.
Zona tunggal Humifog adalah fungsi pemanasan/pendinginan ganda: unit zona tunggal humiFog dapat mendinginkan udara selama musim panas dan melembabkan selama musim dingin. Teknologi pendinginan evaporatif tidak langsung memastikan penghematan energi yang signifikan, artinya investasi dapat dibayar kembali dengan sangat cepat. Humifog singlezone cocok untuk semua

Humifog zona tunggal cocok untuk semua aplikasi yang memerlukan tingkat kebersihan tinggi: unit ini sebenarnya disertifikasi sesuai dengan VDI6022/VDI3803/DIN1946, dan tidak menggunakan biosida kimiawi, melainkan air murni dan sederhana.

Antarmuka pengguna intuitif dan mudah digunakan bahkan untuk pengguna yang kurang ahli. Ini tersedia dalam 5 bahasa (Italia, Inggris, Prancis, Spanyol, dan Jerman disertakan dan dapat diaktifkan kapan saja).

Memiliki :
- Pengontrol elektronik
- Erminal untuk input probe dan kontrol sistem distribusi air yang dikabutkan
- antarmuka grafis pGD1
- Inverter untuk mengontrol kapasitas pompa
- Pengukur konduktivitas
- Ressure dan sensor suhu
- Pompa iston; tersedia dalam versi bebas kuningan, baja tahan karat & silikon
- Peredam getaran

Unit pemompaan
HumiFog menggunakan pompa volumetrik untuk memberi tekanan pada air, yang diatomisasi oleh nozel baja tahan karat khusus. Sistem kontrol yang canggih menggabungkan aksi inverter, yang mengontrol kecepatan dan akibatnya laju aliran pompa, dengan rangkaian katup solenoida yang hanya mengaktifkan nosel yang diperlukan, memungkinkan sistem untuk selalu beroperasi pada tekanan ideal. untuk atomisasi air, di berbagai aliran-laju.

Unit dapat dikonfigurasi untuk beroperasi:

- Dengan kontrol aliran: untuk aplikasi unit penanganan udara, kapasitas pelembab udara dikontrol secara terus-menerus dalam rentang yang luas dengan aksi gabungan inverter dan pengontrolan jumlah nosel menggunakan katup solenoida (hingga 4 sirkuit). Tekanan air dijaga antara 25 dan 70 bar untuk memastikan atomisasi yang sangat halus, dengan tetesan berdiameter 10 hingga 15 µm. Ini menjamin presisi maksimum dan konsumsi daya dan air minimum. Ideal untuk aplikasi pelembapan presisi di musim dingin (1 rak) atau dikombinasikan dengan pendinginan evaporatif tidak langsung (dua rak, saling eksklusif).
- Pada tekanan konstan: tekanan air dijaga konstan (70 bar) terlepas dari permintaan kapasitas di zona yang dilayani. Kapasitas sistem distribusi dimodulasi secara bertahap, hingga 64, sehingga menjamin presisi yang cukup baik. Inverter digunakan untuk membatasi konsumsi daya motor pompa saat permintaan kurang maksimal. Ideal untuk aplikasi langsung di kamar atau di saluran di beberapa zona.

Sistem pelembapan dan pendinginan di unit penanganan udara atau langsung di dalam ruangan. sistem zona tunggal untuk menggunakan satu unit pemompaan dalam rangkaian AHU dengan titik setel independen.

Sistem distribusi saluran.

Rak
Ini dipasok untuk mengukur berdasarkan AHU/saluran dan terdiri dari manifold dengan nozel atomisasi dan kontrol kapasitas serta katup penguras. Nosel baja tahan karat dilengkapi dengan air demineralisasi bertekanan untuk menghasilkan tetesan yang sangat halus, diameter rata-rata 10-15 µm, yang mudah diserap oleh udara.

Pemisah tetesan
Pemisah tetesan bertujuan untuk menjebak tetesan air yang tidak sepenuhnya menguap, untuk mencegahnya keluar dari ruang pelembab. Ini dibuat sepenuhnya dari baja tahan karat AISI304, baik bahan penyaringan maupun struktur saluran pembuangan.

Sistem pembagian ruangan.
Ini terdiri dari manifold baja tahan karat dengan nosel yang dipasang di dalam ruangan yang dilembabkan/didinginkan. Blower dengan kipas tangensial untuk menghasilkan aliran udara juga tersedia. Aliran udara membantu penguapan tetesan dan membawa tetesan di atas bantalan udara, memastikan lintasan horizontal yang esensial. Humifogsinglezone mengontrol katup solenoid untuk mengontrol kapasitas sistem dan untuk menguras dan mencuci sistem secara otomatis.

Untuk aplikasi pelembapan dan/atau pendinginan di AHU, lingkungan industri, atau sistem AC luar ruang: unit pemompaan secara independen mengontrol suhu/kelembaban di lingkungan terkontrol. Modulasi kapasitas berkelanjutan untuk meminimalkan konsumsi air dan daya. Cocok untuk aplikasi presisi (±2%).

Penjernih Udara, Dehumidifier, & Humidifier

UA100HD301 - Carel Pump for Humifog Humidifier, Adiabatic Humidifier, 100kg/hr single zone stainless pump.

The Humifog UA100HD301 - 100kg/hr single zone stainless pump is the dual heating/cooling function: a humiFog singlezone unit can both cool the air during the summer and humidify during the winter. Indirect evaporative cooling technology ensures significant energy savings, meaning the investment can be paid back very quickly. Humifog singlezone is suitable for all.Humifog singlezone is the dual heating/cooling function: a humiFog singlezone unit can both cool the air during the summer and humidify during the winter. Indirect evaporative cooling technology ensures significant energy savings, meaning the investment can be paid back very quickly. Humifog singlezone is suitable for all

Humifog singlezone is suitable for all applications that require a high level of hygiene: the unit is in fact certified in accordance with VDI6022/VDI3803/DIN1946, and does not use chemical biocides, but rather pure and simple wate.

The user interface is intuitive and easy to use even for less expert users. It is available in 5 languages (Italian, English, French, Spanish and German are included and can be activated at any time).

It has :
- Electronic controller
- Erminals for probe inputs andcontrol of the atomised waterdistribution system
- pGD1 graphic interface
- Inverter to control pump capacity
- Conductivity meter
- Ressure and temperature sensors
- Iston pump;available in brass,stainless steel & silicon free versions
- Vibration damper

Pumping unit
HumiFog uses a volumetric pump to pressurise the water, which is atomised by special stainless steel nozzles. The sophisticated control system combines the action of an inverter, which controls the speed and consequently the flow-rate of the pump, with a series of solenoid valves that activate only the nozzles that are necessary, allowing the system to always operate at the ideal pressure to atomise the water, across a wide range of flow-rates.

The unit can configured to operate:

- With flow control: for air handling unit applications, the capacity of the humidifier is controlled continuously across a wide range by the combined action of an inverter and controlling the number of nozzles using solenoid valves (up to 4 circuits). The water pressure is kept between 25 and 70 bars to ensure very fine atomisation, with droplets from 10 to 15 µm in diameter. This guarantees maximum precision and minimum power and water consumption. Ideal for precision humidification applications in winter (1 rack) or in combination with indirect evaporative cooling (two racks, mutually exclusive).
- At constant pressure: the water pressure is kept constant (70 bars) regardless of the capacity demand in the zone being served. The capacity of the distribution system is modulated in steps, up to 64, thus guaranteeing quite fine precision. The inverter is used to limit the power consumption of the pump motor when demand is less than maximum. Ideal for applications directly in rooms or in ducts in multiple zones.

Humidification and cooling system in air handling units or directly in the room. singlezone systems to use one pumping unit in a series of AHUs with independent set point.

Duct distribution system.

Rack
This is supplied to measure based on theAHU/duct and is made up of manifoldswith atomisation nozzles and capacitycontrol and drain valves. The stainlesssteel nozzles are supplied with pressuriseddemineralised water to generate veryfine droplets, average diameter 10-15 µm,which are readily absorbed by the air.

Droplet separator
The droplet separator has the purpose oftrapping the droplets of water that are notcompletely evaporated, to prevent themfrom leaving the humidification chamber.It is made completely from AISI304stainless steel, both the filtering materialand the drain structure.

Room distribution system.
This is made up of stainless steel manifoldswith nozzles installed inside the roombeing humidified/cooled. Blowers withtangential fans to generate a flow of airare also available. The flow of air assistsevaporation of the droplets and carries thedroplets on a cushion of air, ensuring anessentially horizontal trajectory. Humifogsinglezone controls solenoid valves to control the capacity of the system and todrain and automatically wash the system.

For humidification and/or cooling applications in an AHU, industrial environment or outdoor air-conditioning system: a pumping unit independently controls the temperature/humidity in the controlled environment. Continuous modulation of capacity to minimise water and power consumption. Suitable for precision applications (±2%).

Control models : Single zone pumping unit
Rated capacity kg/h : 100
Power supply : 230 V, 1 phase, 50 Hz or 208 V, 1 phase, 60 Hz
Pumping unit power consumption kW : 0.955
Zone controller power consumption kW : 0.28
Operating conditions : 1T40 °C <80 % RH non-condensing
Storage conditions : 1T50 °C <80 % RH non-condensing
Index of protection : IP20

Certificazions
Hygienic certification for air-conditioning generic applications : VDI 6022, page 1 (04/06), VDI 3803 (10/02), ONORM H 6021 (09/03), SWKI VA104-01 (04/06), DIN EN 13779 (09/07)
Hygienic certification for hospital applications : DIN 1946, part 4 (01/94), ONORM H 6020 (02/07)*, SWKI 99-3 (03/04)
Certification : CE and ETL998 (pumping unit); ETL508A (zone controllers)

Water inlet
Connection : G3/4”F (NPT3/4F for UL versions)
Temperature limits : 1T40 ºC / 34T104 ºF
Pressure limits : 0.3 to 0.8 Mpa
Total hardness (ppm CaCO3) : 0 to 25
Conductivity limit μS/cm : 0 to 50 μS/cm (stainless steel pump) – 30 to 50 μS/cm (brass pump)
pH : 6.5 to 8.5

Water outlet
Connection : M16.5m DIN 2353 (G3/8”F) (NPT3/8F for UL versions)

Water drain
Connection : Stainless steel pipe, OD 10 mm/ 0.4 inch
Serial communication : CAREL, Modbus® protocol (others optional)

Control
Control : External signal, temperature or humidity control; plus temperature or humidity limit probe
Type of input signals : 0 to 1 V, 0 to 10 V, 2 to 10 V, 0 to 20 mA, 4 to 20 mA, NTC

Dimensions and weights
Pumping unit dimensions (LxWxH) mm : 1030 x 400 x 860 mm
Pumping unit weight kg : 85
Zone controller dimensions (LxWxH) mm : 500 x 150 x 580 mm
Zone controller weight kg : 19.5